DESIGNED FOR USE
IN MEDICAL ENVIRONMENT |
|
SPECIFICALLY DESIGNED FOR USE IN ASSOCIATION WITH EARTH LEAKAGE
CONTROL SYSTEMS |
| POWER |
INPUT |
OUTPUT |
FREQUENCY |
STANDARDS |
| FROM
3150 TO 25000VA |
230V
|
230V
|
50/60
Hz |
EN
61558-2-15 |
| CEI
64-4 |
| CEI
96-2 |
| BS
3535 |
Open type
Protection IP00
Isolation class H (At max 45°C)
Separate copper windings cl. H
Resing impregnated and tropicalised
Double earthed copper screen between primary and secondary
Central point of sec. winding available to be earthed
Short circuit voltage < 3%
Inrush current < 12 In
Connections on terminal blocks up to 10kVA (or to 63A)
Connections on brass bolts up to 12,5kVA (or from 64A)
Optional: mounted in metal enclosure RAL7032, IP23
|


|
 |
| power |
part.
no. |
losses |
short
circ. |
regulation |
dimensions
mm. |
DWG |
weight |
box |
| VA |
W |
voltage
% |
% |
A |
B |
C |
D |
E |
F |
kg. |
code |
| 3150 |
TMI6403 |
130 |
3.0 |
3.0 |
240 |
230 |
320 |
200 |
125 |
12 |
A |
34.0 |
SA02 |
| 4000 |
TMI6404 |
145 |
2.9 |
2.6 |
240 |
240 |
320 |
200 |
135 |
12 |
A |
38.0 |
SA02 |
| 5000 |
TMI6405 |
180 |
2.7 |
2.6 |
240 |
250 |
320 |
200 |
145 |
12 |
A |
44.0 |
SA02 |
| 6300 |
TMI6406 |
200 |
2.7 |
2.6 |
280 |
230 |
400 |
220 |
145 |
12 |
A |
49.0 |
SA03 |
| 8000 |
TMI6408 |
210 |
2.7 |
2.6 |
280 |
240 |
400 |
220 |
155 |
12 |
A |
60.0 |
SA03 |
| 10000 |
TMI6410 |
280 |
2.5 |
2.3 |
280 |
250 |
400 |
220 |
165 |
12 |
A |
65.0 |
SA03 |
| 15000 |
TMI6415 |
400 |
2.5 |
2.2 |
320 |
260 |
450 |
260 |
185 |
12 |
B |
92.0 |
SA04 |
| 20000 |
TMI6420 |
600 |
2.4 |
2.0 |
320 |
280 |
450 |
260 |
205 |
12 |
B |
116.0 |
SA04 |
| 25000 |
TMI6425 |
700 |
2.1 |
2.0 |
320 |
280 |
450 |
260 |
205 |
12 |
B |
131.0 |
SA04 |
| ASK
FOR CODES AND SPECIFICATION OF HIGHER RATINGS |
|
 |
 |
|
A |
B |
|
PART NO
SHOWN ABOVE REPRESENT THE STANDARD IN.230V-OUT.230V TYPE. IF
DIFFERENT INPUT-OUTPUT VLTAGES ARE REQUIRED, THERE MUST BE
SPECIFIED IN THE DESCRIPTION OF YOUR ORDER. |
|
IF
SECONDARY VOLTAGE IS BELOW 50V a.c. TMI64 TRANSFORMERS ARE ALSO
MANUFACTURED IN STRICT CONFORMITY WITH EN61558-2-6 FOR SAFETY
ISOLATION TRANSFORMERS |
 |
|
ACCESSORI
EARTH LEAKAGE CONTROL SYSTEMS
TEMPERATURE
MONITOR RELAY WITH ALARM AND TRIP |
|